- Basis
- Required by law (EU F-gas Regulation)
- From
- 5 tonnes CO2 equivalent
- Interval
- 5 to 50 t: every 12 months, 24 with leak detection
- Who
- A certified company
How often?
- From 5 to 50 tonnes CO2 equivalent: every 12 months, every 24 months with automatic leak detection.
- From 50 to 500 tonnes: every 6 months, every 12 months with leak detection.
- From 500 tonnes: every 3 months. Leak detection is required here, and with it the interval is every 6 months.
- Hermetically sealed equipment labelled as such under 10 tonnes CO2 equivalent is exempt.
What to arrange
- Know how much refrigerant each system holds, converted to CO2 equivalent.
- A certified company for checks, maintenance and repairs.
- A logbook per system with checks, leaks and top-ups.
In Klantpunt
In Klantpunt you plan the leak check per system with the interval that matches its charge, with a reminder in advance. You note the refrigerant and charge on the asset, and the report of each check is in the file.
This is general guidance based on Dutch rules. What applies to your building depends on use, size and permit; check with your adviser, the standard or the authorities. Updated 17 November 2026.